Журнал Российского общества по неразрушающему контролю и технической диагностике
The journal of the Russian society for non-destructive testing and technical diagnostic
 
| Русский Русский | English English |
 
Главная
10 | 10 | 2026
Баннер
2018, 05 May

DOI: 10.14489/td.2018.05.pp.032-037

 

Kondratenko V. S., Rogov A. Yu., Sakunenko Yu. I., Sorokin A. V.
DEVELOPMENT OF METHODS TO DETERMINE THE SIZE AND LOCATION OF WATER LEAKS WITH THE HELP OF SORPTION OF HYDRO-SENSOR CABLE
(pp. 32-37)

Abstract. The work proves the possibility of determining the locations and sizes of water leaks (breakthroughs of water vapor) on the basis of measurements of changes of electric parameters of sorption hydro sensor cable (SHC). Investigated by potentiometric, reflectometric method of measurement and the capacity of SHC to determine the locations and sizes of the impact of water or vapor. It is established that SHC allows to identify the first signs of a water leak (breakthrough of water vapor): spots of dampness; condensation; micro droplets; micro leakage. Experimentally set threshold of sensitivity of the SHC – 0.05 gwater. Hardware implementation of the studied methods will allow you to create an alarm system that will provide detection of the location and size of emergency situations involving water leaks (breakthroughs of water vapor) in the early stages, which will reduce damages by taking preventive measures to prevent its development.

Keywords: sorption hydro sensor cable, leak, water, water vapor, potentiometry, reflectometry, capacitance.

 

V. S. Kondratenko, A. Yu. Rogov (Federal State Budget Educational Institution of Higher Education “Moscow Technological University”, Moscow, Russia)
Yu. I. Sakunenko, A. V. Sorokin (LLC “Engimatic”, Moscow, Russia)

 

 

1. Water leakage sensors GIDROLOCK. Available at: http://gidrolock.ru/production/datchiki-protechki-vody-gidrolock/ (Accessed: 30.01.2018). [in Russian language]
2. Cable monitoring system for water leakage Thermocable Pro H2O. Available at: http://flamestop.ru/termokabel-datchik-protechek (Accessed: 30.01.2018). [in Russian language]
3. Kondratenko V. S., Sakunenko Iu. I. (2015). Sorption gensensor cable - new features. RITM, (1), pp. 40-42. [in Russian language]
4. Kondratenko V. S., Sakunenko Iu. I., Burliai D. A. (2016). New achievements in hydrosensorics. Pribory, (9), pp. 28-31. [in Russian language]
5. Sakunenko Iu. I., Kondratenko V. S. (2015). Leak detector for electrically conductive liquids. Ru Patent No. 2545485. Russian Federation. [in Russian language]
6. Search technology for cable defects using a reflectometer: Soaked cable sections. Available at: http://www.tdse.ru/info/ arti-cles/reflektom_mc_07 (Accessed: 30.01.2018). [in Russian language]
7. Reis-105M1. Manual. Available at: http://www.tdse. ru/info/articles/reflektom_mc_07 (Accessed: 30.01.2018). [in Russian language]

 

 

This article  is available in electronic format (PDF).

DOI: 10.14489/td.2018.05.pp.032-037

Copy the article DOI and follow the link https://id-spektr.ru/product/pokupka-elektronnoy-stati-iz-zhurnala-kontrol-diagnostika

Please specify the article DOI in the order comments.